Source: Alexander S Rattner and Christopher J Greer; Department of Mechanical and Nuclear Engineering, The Pennsylvania State University, University Park, PA
This experiment demonstrates the principles of vapor compression refrigeration. The vapor compression cycle is the dominant refrigeration technology, found in most refrigerators, freezers, air-conditioning systems, and heat pumps. In this cycle, cooling (heat acquisition) is achieved with low-pressure evaporation of refrigerant. Thermal energy absorbed in evaporation is rejected to the surroundings through high-pressure refrigerant condensation. Mechanical work is applied in the compressor to raise the working fluid from low to high pressure.
While refrigeration technology is ubiquitous, the concealing packaging and autonomous operation of most refrigerators makes it difficult to appreciate the operating principles and function of key components. In this experiment, a rudimentary vapor compression refrigerator is constructed. The compressor is manually actuated with a bicycle pump, allowing intuitive appreciation of cycle operation as the experimenter becomes part of the system. Resulting component pressures and temperatures can be interpreted in terms of the thermodynamic T-s and P-h diagrams, which capture the variation of fluid properties from the liquid-to-vapor states (during evaporation and condensation).
The vapor compression cycle is comprised of four main components: the vapor compressor, condenser (high-temperature heat rejection), expansion device, and evaporator (low-temperature heat acquisition) (Fig. 1). The cycle can be described with four key state points.
• 1 → 2: Low pressure vapor refrigerant flows into the compressor, and is compressed to the high-side pressure.
• 2 → 3: Pressurized refrigerant vapor condenses to the liquid phase isobarically (constant pressure), rejecting heat to the surroundings.
• 3 → 4: Liquid refrigerant flows through the throttling expansion device isenthalpically (constant enthalpy), flashing to a two-phase state as its pressure drops. This lowers the refrigerant temperature to the saturation temperature at the low-side pressure.
• 4 → 1: Low temperature refrigerant receives heat from the surroundings and continues to evaporate as it flows through the evaporator isobarically.
The transitions between these state points can be mapped out on thermodynamic diagrams. In these temperature-entropy (T-s, Fig. 2a) and pressure-enthalpy (P-h, Fig. 2b) diagrams, the left side of the dome represents the liquid phase and the right side represents the vapor phase. Inside the vapor dome, the fluid is two-phase and temperature is a function of pressure. The energy transfer to or from the system in each stage of the process can be evaluated by the change in enthalpy multiplied by the refrigerant mass flow rate (positive change: energy acquisition, negative: heat rejection to surroundings). Consider a representative air-conditioning system using R-134a refrigerant at a flow rate of = 0.01 kg s-1 with the following state point values (Table 1).
Table 1 - Representative refrigeration cycle state points
Point | Pressure (P, kPa) |
Temperature (T, °C) |
Enthalpy (h, kJ kg-1) |
Entropy (s, kJ kg-1 K-1) |
Quality (Q) |
1 | 402.2 | 17.0 | 263.0 | 0.953 | 1 |
2 | 815.9 | 57.1 | 293.6 | 1.000 | 1 |
3 | 815.9 | 32.0 | 96.5 | 0.357 | 0 |
4 | 402.2 | 9.1 | 96.5 | 0.363 | 0.169 |
Here, the cooling capacity in the evaporator is evaluated as = 1.67 kW. The compressor work input is
= 0.31 kW. The system efficiency, or coefficient of performance (COP), is
= 5.4.
Figure 1: Schematic of the vapor compression refrigeration cycle
Figure 2: T-s (a) and P-h (b) diagrams for the representative R-134a vapor compression cycle with state points listed in Table 1.
Caution: This experiment involves systems at elevated pressures and use of refrigerants, which can be toxic at high concentrations. Ensure reasonable safety precautions are followed and that appropriate PPE is worn. Ensure adequate ventilation when working with refrigerants.
1. Fabrication of refrigeration system (see diagram and photograph, Fig. 3)
Figure 3: a. Diagram of components and connections in experimental vapor compression refrigeration system. Please click here to view a larger version of this figure.
Figure 4: T - s (a) and P - h (b) diagrams for experimental R-134a vapor compression refrigeration cycle.
2. Charging the refrigeration system
3. Operation
Phigh | 659 ± 7 kPa | ||
Plow | 569 ± 7 kPa | ||
Tambient | 22.0 ± 1 °C | ||
Tcond | 25.0 ± 1 °C | Tsat,R-134a (Phigh) | 24.7 ± 0.3 °C |
Tevap | 21.1 ± 1°C | Tsat,R-134a (Plow) | 19.8 ± 0.4 °C |
Table 2. Refrigeration system measured properties.
Measured condenser and evaporator outer surface temperatures are relatively close to the saturation temperatures at Phigh and Plow. The evaporator temperature is slightly higher than Tsat,R-134a (Plow), possibly due to heat transfer from the ambient air to the exterior thermocouple. The condenser temperature is slightly higher than Tsat,R-134a (Plow), but within experimental uncertainty. This temperature may also be measured in the warmer super-heated portion of the condenser.
Approximate T-s and P-h cycle diagrams for this system are presented in Fig. 4.
This experiment demonstrated the principles of vapor compression refrigeration. Admittedly, the experimental system yields limited performance - with a low cooling capacity (Qevap) and low lift (evaporator-to-ambient temperature difference). However, it offers an intuitive introduction to the design and physics of vapor compression. The data analysis steps demonstrate the use of T-s and P-h diagrams to describe thermodynamic cycle operation.
Much of the input work is expended in compressing air in the bicycle pump. Using a lower pressure refrigerant (e.g., R1234ze(E)) would reduce this work and may allow greater evaporator-to-condenser temperature differences. Additionally, the expansion valve employed here could only maintain relatively small low-to-high side pressure differences. An alternate valve with finer adjustment control may be preferable. In most commercial refrigeration systems, a temperature controlled expansion valve (TXV) is used, which dynamically adjusts its opening to maintain a desired evaporator temperature.
The vapor compression cycle is the most widely used refrigeration technology. It is found in almost all household air conditioners and refrigerators as well as industrial scale chillers and freezers. The cycle can also be used as a heat pump. In this mode, it acquires heat in the evaporator from the low temperature surroundings, and delivers it to a warmer conditioned space. This can be an efficient mode of heating compared to direct resistance heating because most of the delivered heat is drawn from the surroundings and only a small portion is supplied to the compressor as mechanical work.
This experiment also demonstrates the use of thermodynamic T-s and P-h diagrams. These are critical tools for analysis and engineering of numerous energy systems including chemical processing operations, refrigeration cycles, and power generation.
Перейти к...
Видео из этой коллекции:
Now Playing
Mechanical Engineering
24.6K Просмотры
Mechanical Engineering
29.9K Просмотры
Mechanical Engineering
22.4K Просмотры
Mechanical Engineering
21.6K Просмотры
Mechanical Engineering
58.0K Просмотры
Mechanical Engineering
7.7K Просмотры
Mechanical Engineering
40.9K Просмотры
Mechanical Engineering
28.0K Просмотры
Mechanical Engineering
15.5K Просмотры
Mechanical Engineering
13.5K Просмотры
Mechanical Engineering
11.8K Просмотры
Mechanical Engineering
10.7K Просмотры
Mechanical Engineering
7.4K Просмотры
Mechanical Engineering
22.6K Просмотры
Mechanical Engineering
26.0K Просмотры
Авторские права © 2025 MyJoVE Corporation. Все права защищены