Source: Ali Bazzi, Department of Electrical Engineering, University of Connecticut, Storrs, CT.
Variable frequency drives (VFDs) are a type of adjustable speed drive, which are becoming standard equipment to power most AC induction motors. VFDs are common in industrial and automation applications and typically provide robust control of the motor in speed, torque, or position modes. The VFDs tested and simulated in this experiment focus on speed and open-loop control with constant voltage to frequency ratio (V/f) control. The induction motor typically operates at a rated stator flux, and this flux is approximately proportional to the V/f ratio. To maintain constant stator flux, the voltage and frequency applied to the stator are maintained at a constant ratio, which is the V/f ratio. The VFD used in this experiment is a 1 hp Yaskawa V1000 drive, but the procedure applies to most commercially available general purpose drives.
VFDs typically include a rectifier stage for AC/DC conversion, followed by an inverter stage for DC/AC inversion. The inverter and rectifier may be single-phase to supply single-phase motors or three-phase to supply three-phase motors. Rectifiers may also have a power factor correction stage, so the VFD and motor are seen at a high power factor from the grid side supplying the rectifier, to reduce current drawn from the grid into the VFD and motor. Inverters are usually switched with pulse width modulation (PWM), which is a switching pattern very close to a sinusoid. Having PWM voltages fed from the inverter into the motor makes the motor see voltages close enough to sinusoids, since most motors are designed to be line-fed (i.e., directly fed by the grid). In PWM switching, the VFD can adjust based on user input or by automatically controlling the frequency of the sinusoid into the motor and the voltage magnitude. Most commercial VFDs use open-loop control, where the V/f ratio is maintained as constant, when operating the motor at or below rated voltage; this maintains motor flux at a rated value. Other more advanced VFDs use "vector control," which is a closed-loop control scheme that provides tight speed or torque regulation.
1. Make sure the three-phase disconnect switch is off.
2. Check that the VARIAC is at 0%.
3. Perform the following connections at the machine and VARIAC terminals:
4. Press the "Lo/Re" button once to put the drive in local mode - the redlight on that button should turn on.
5. Check that the drive parameters are the same as those shown in Table 1.
6. To perform basic voltage, current, and frequency measurements:
7. To set a different output frequency, and thus set a different motor speed since speed and electrical frequency are proportional:
8. Set the frequency to 10 Hz.
9. Note that if the drive overloads or faults: Press the red "Stop" button, and then press the > (right arrow/reset) button.
Table 1: Main VFD Settings
VFDs typically provide a constant voltage-to-frequency ratio to maintain stator flux in an induction machine close to a constant. If a machine is rated at 60 Hz and 208 V (line-to-line, RMS), then the V/f ratio is 208/60 = 3.467 V/Hz. Therefore, when the machine is run at a lower frequency to reduce its speed, the voltage is weakened to maintain a V/f ratio at a constant. For example, if the machine is run at 30 Hz, voltage should be reduced to 104 V. Or, if the machine is run at a frequency of 15 Hz, then the voltage should be reduced to 52 V. Under no load conditions, current typically drops as voltage drops, since the machine's reactance drop with lower frequencies.
At higher than rated frequencies, VFDs are usually programmed to maintain rated voltage; therefore, a constant V/f does not apply. This is mainly due to the voltage ratings of the machine, where higher voltages than rated are kept away from to avoid breaking the machine insulation or causing more current to flow into the machine. For example, if the frequency for a 60 Hz machine is set at 70 Hz using a VFD, the voltage is maintained at 208 V instead of 242.67 V.
VFDs have a wide use in commercial, industrial, and automation systems, and they can save significant amounts of energy, as they adjust the operating point of a motor to draw as much energy as needed under variable speed operation. Inverters used in VFDs are also common in many motor control applications including transportation systems with more electric vehicles, in heating, ventilation, and air conditioning applications, and many others.
Przejdź do...
Filmy z tej kolekcji:
Now Playing
Electrical Engineering
6.9K Wyświetleń
Electrical Engineering
144.6K Wyświetleń
Electrical Engineering
15.0K Wyświetleń
Electrical Engineering
12.4K Wyświetleń
Electrical Engineering
56.9K Wyświetleń
Electrical Engineering
21.1K Wyświetleń
Electrical Engineering
13.2K Wyświetleń
Electrical Engineering
20.1K Wyświetleń
Electrical Engineering
23.4K Wyświetleń
Electrical Engineering
17.5K Wyświetleń
Electrical Engineering
17.9K Wyświetleń
Electrical Engineering
23.4K Wyświetleń
Electrical Engineering
11.6K Wyświetleń
Electrical Engineering
21.6K Wyświetleń
Electrical Engineering
14.2K Wyświetleń
Copyright © 2025 MyJoVE Corporation. Wszelkie prawa zastrzeżone