VFD-fed AC Induction Machine

Przegląd

Source: Ali Bazzi, Department of Electrical Engineering, University of Connecticut, Storrs, CT.

Variable frequency drives (VFDs) are a type of adjustable speed drive, which are becoming standard equipment to power most AC induction motors. VFDs are common in industrial and automation applications and typically provide robust control of the motor in speed, torque, or position modes. The VFDs tested and simulated in this experiment focus on speed and open-loop control with constant voltage to frequency ratio (V/f) control. The induction motor typically operates at a rated stator flux, and this flux is approximately proportional to the V/f ratio. To maintain constant stator flux, the voltage and frequency applied to the stator are maintained at a constant ratio, which is the V/f ratio. The VFD used in this experiment is a 1 hp Yaskawa V1000 drive, but the procedure applies to most commercially available general purpose drives.

Zasady

VFDs typically include a rectifier stage for AC/DC conversion, followed by an inverter stage for DC/AC inversion. The inverter and rectifier may be single-phase to supply single-phase motors or three-phase to supply three-phase motors. Rectifiers may also have a power factor correction stage, so the VFD and motor are seen at a high power factor from the grid side supplying the rectifier, to reduce current drawn from the grid into the VFD and motor. Inverters are usually switched with pulse width modulation (PWM), which is a switching pattern very close to a sinusoid. Having PWM voltages fed from the inverter into the motor makes the motor see voltages close enough to sinusoids, since most motors are designed to be line-fed (i.e., directly fed by the grid). In PWM switching, the VFD can adjust based on user input or by automatically controlling the frequency of the sinusoid into the motor and the voltage magnitude. Most commercial VFDs use open-loop control, where the V/f ratio is maintained as constant, when operating the motor at or below rated voltage; this maintains motor flux at a rated value. Other more advanced VFDs use "vector control," which is a closed-loop control scheme that provides tight speed or torque regulation.

Procedura

1. Make sure the three-phase disconnect switch is off.

2. Check that the VARIAC is at 0%.

3. Perform the following connections at the machine and VARIAC terminals:

  1. Connect the induction machine stator terminals to the drive output (right-side connectors, when looking at the front of the drive).
  2. Connect the drive input (left-hand set of connectors, when looking at the front of the drive) to the VARIAC output.
  3. Connect the VARIAC input to the three-phase receptacle on the bench.
  4. Before power is applied, turn the dial on the VARIAC up to 75%. This starts the drive at about 210 V line-to-line later in the experiment.
  5. Turn on the three-phase disconnect switch. The main screen on the VFD should turn on and display "F000".

4. Press the "Lo/Re" button once to put the drive in local mode - the redlight on that button should turn on.

  1. The "Lo/Re" button allows the user to make a selection between the local (Lo) frequency setting and the remote (Re) frequency setting.
  2. The user is able to change the frequency (f), and the drive automatically sets the corresponding voltage (V) to maintain a constant V/f ratio.

5. Check that the drive parameters are the same as those shown in Table 1.

6. To perform basic voltage, current, and frequency measurements:

  1. Cycle through the menu and find the display with a "0.0u" after it - this displays the measurement of the voltage fed to the motor.
  2. From there, scroll up once to a screen that reads "0.00A" - this displays the current measurement when the drive is running.
  3. The next screen up from that reads "0.00" - this is the frequency measurement.

7. To set a different output frequency, and thus set a different motor speed since speed and electrical frequency are proportional:

  1. Go back to the main screen and search for the letter F.
    1. Change the frequency by pressing enter and then manipulating the value using the up and down arrows.
    2. Use the > (right arrow/reset) button to change between the column of values.
    3. Enact any changes by pressing enter.
    4. Cancel changes and continue to run at the present frequency by pressing "Esc."

8. Set the frequency to 10 Hz.

  1. Press the green "Run" button.
  2. Scroll to the voltage, current, and frequency readings and record their values.
  3. Repeat for the following frequencies: 25, 45, 60, and 70 Hz.
  4. Note that a maximum frequency limit might have been set to prevent the user from exceeding 60 Hz, so adjust the maximum frequency limit from the "E2" menu.

9. Note that if the drive overloads or faults: Press the red "Stop" button, and then press the > (right arrow/reset) button.

Table 1
Table 1: Main VFD Settings

Wyniki

VFDs typically provide a constant voltage-to-frequency ratio to maintain stator flux in an induction machine close to a constant. If a machine is rated at 60 Hz and 208 V (line-to-line, RMS), then the V/f ratio is 208/60 = 3.467 V/Hz. Therefore, when the machine is run at a lower frequency to reduce its speed, the voltage is weakened to maintain a V/f ratio at a constant. For example, if the machine is run at 30 Hz, voltage should be reduced to 104 V. Or, if the machine is run at a frequency of 15 Hz, then the voltage should be reduced to 52 V. Under no load conditions, current typically drops as voltage drops, since the machine's reactance drop with lower frequencies.

At higher than rated frequencies, VFDs are usually programmed to maintain rated voltage; therefore, a constant V/f does not apply. This is mainly due to the voltage ratings of the machine, where higher voltages than rated are kept away from to avoid breaking the machine insulation or causing more current to flow into the machine. For example, if the frequency for a 60 Hz machine is set at 70 Hz using a VFD, the voltage is maintained at 208 V instead of 242.67 V.

Wniosek i Podsumowanie

VFDs have a wide use in commercial, industrial, and automation systems, and they can save significant amounts of energy, as they adjust the operating point of a motor to draw as much energy as needed under variable speed operation. Inverters used in VFDs are also common in many motor control applications including transportation systems with more electric vehicles, in heating, ventilation, and air conditioning applications, and many others.

Tagi

VFD fed AC Induction MachineVariable frequency DrivesVFDsInduction MotorsOptimal PerformanceSoft StartStarting TorquesSurge CurrentsMechanical StressesEquipment LifeReliabilityEnergy SavingsConfigurationThree phase AC Induction MotorStatorRotorAC Frequency

Przejdź do...

0:06

Overview

1:20

Principles of Variable Frequency Drives

6:05

Configuring a Variable Frequency Drive Controller

8:56

Applications

10:06

Summary

Filmy z tej kolekcji:

article

Now Playing

VFD-fed AC Induction Machine

Electrical Engineering

6.9K Wyświetleń

article

Electrical Safety Precautions and Basic Equipment

Electrical Engineering

144.6K Wyświetleń

article

Characterization of Magnetic Components

Electrical Engineering

15.0K Wyświetleń

article

Introduction to the Power Pole Board

Electrical Engineering

12.4K Wyświetleń

article

DC/DC Boost Converter

Electrical Engineering

56.9K Wyświetleń

article

DC/DC Buck Converter

Electrical Engineering

21.1K Wyświetleń

article

Flyback Converter

Electrical Engineering

13.2K Wyświetleń

article

Single Phase Transformers

Electrical Engineering

20.1K Wyświetleń

article

Single Phase Rectifiers

Electrical Engineering

23.4K Wyświetleń

article

Thyristor Rectifier

Electrical Engineering

17.5K Wyświetleń

article

Single Phase Inverter

Electrical Engineering

17.9K Wyświetleń

article

DC Motors

Electrical Engineering

23.4K Wyświetleń

article

AC Induction Motor Characterization

Electrical Engineering

11.6K Wyświetleń

article

AC Synchronous Machine Synchronization

Electrical Engineering

21.6K Wyświetleń

article

AC Synchronous Machine Characterization

Electrical Engineering

14.2K Wyświetleń

JoVE Logo

Prywatność

Warunki Korzystania

Zasady

Badania

Edukacja

O JoVE

Copyright © 2025 MyJoVE Corporation. Wszelkie prawa zastrzeżone